Wyłączniki powietrzne (ACB) AE-SW
Wyłączniki powietrzne (ACB) AE-SW
Wyłączniki niskiego napięcia Wyłączniki powietrzne
Tego rodzaju wyłączniki zaspokajają różne potrzeby i używane są jako główne wyłączniki zasilania, np. budynków, fabryk, statków itp.

 

 

SUPER AE – WORLD SUPER SERIES

AE1000-SW

AE1250-SW

Frame size

A

1000

1250

Rated insulation voltage (AC V) 50/60 Hz

U i

1000

1000

Rated operating voltage (AC V) 50/60 Hz

U e

690

690

Rated impulse withstand voltage (kV)

U imp

12

12

Pollution degree

 

3

3

Number of poles

P

3 / 4

3 / 4

Rated curren t I n (CT rating)

1000

1250

Adjustment range Rated current I r (A)

General use (current rating adjustable

0.5 to 1.0 x I n 0.05 step)

500-550-600-650- 700-750-800-850- 900-950 -1000

625-687.5-750-812.5- 875-937.5-1000-1062.5-1125-1187.5-1250

Generator protection (current rating fixed)

400 ≤ I r ≤ 1000

800 ≤ I r ≤ 1250

Rated current of neutral pole

A

1000

1250

IEC 60947-2, EN 60947-2, VDE, JIS C 8201-2-1

Ultimate breaking capacity I cu (kA rms)

 

690 V AC

65

65

600 V AC

65

65

240–500 V AC

65

65

With MCR

690 V AC

65

65

600 V AC

65

65

240–500 V AC

65

65

Without instantaneous

690 V AC

25 a

25 a

500 V AC

25 a

25 a

Rated service breaking capacity Ics (kA rms) % l cu

   

Rated making capacity I cm (kA, peak)

 

690 V AC

143

143

 

600 V AC

143

143

240–500 V AC

143

143

With MCR

690 V AC

143

143

600 V AC

143

143

240–500 V AC

143

143

Without instantaneous

690 V AC

52.5

52.5

500 V AC

52.5

52.5

Disconnector: switching capacity (6x I r at 690V AC)

O

O

Rated short time withstand current (kA rms)  I cw

1 s

65

65

2 s

60

60

3 s

50

50

Maximum total breaking time

ms

40 f

40 f

Closing time

ms

80

80

Number of operating cycles (ON/OFF) b

With rated current

500 V AC I n

5000

5000

690 V AC I n

5000

5000

Without rated current d

25000

25000

Connecting terminal

Horizontal terminal

O

O

Vertical terminal

O

O

Front terminal

O

O

Dimensions (HxWxD) mm

Fixed type

3-pole

410x340x290

410x340x290

4-pole

410x425x290

410x425x290

Drawout type

3-pole

430x300x368

430x300x368

4-pole

430x385x368

430x385x368

Weight kg

Fixed type

3-pole

41

41

4-pole

51

51

Drawout type (with cradle)

3-pole

64

64

4-pole

78

78

Cradle only

3-pole

26

26

4-pole

30

30

 

  1. The columns for “without instantaneous” are the values when the bare main body and the external relay is combined.
  2. The number of operating cycles without rated current also include the number of operating cycles with rated current.
  3. AE4000-SW, AE5000-SW, AE6300-SW, AE2000-SWA and AE4000-SWA apply for only vertical terminal of connecting terminal.
  4. This value means number of operating cycles of ACB's body not including accessories.
  5. Products with low rating types is available.

 

 

SUPER AE – WORLD SUPER SERIES

AE2000-SW

AE2500-SW

Frame size

A

2000

2500

Rated insulation voltage (AC V) 50/60 Hz

U i

1000

1000

Rated operating voltage (AC V) 50/60 Hz

U e

690

690

Rated impulse withstand voltage (kV)

U imp

12

12

Pollution degree

 

3

3

Number of poles

P

3 / 4

3 / 4

Rated curren t I n (CT rating)

2000

2500

Adjustment range Rated current I r (A)

General use (current rating adjustable

0.5 to 1.0 x I n 0.05 step)

1000-1100-1200-1300- 1400-1500-1600-1700- 1800-1900-2000 e

1250-1375-1500-1625- 1750-1875-2000-2125- 2250-2375-2500

Generator protection (current rating fixed)

800 ≤ I r ≤ 2000

1600 ≤ I r ≤ 2500

Rated current of neutral pole

A

2000

2500

IEC 60947-2, EN 60947-2, VDE, JIS C 8201-2-1

Ultimate breaking capacity I cu (kA rms)

 

690 V AC

75

75

600 V AC

75

75

240–500 V AC

85

85

With MCR

690 V AC

75

75

600 V AC

75

75

240–500 V AC

75

75

Without instantaneous

690 V AC

45 a

45 a

500 V AC

45 a

45 a

Rated service breaking capacity Ics (kA rms) % l cu

100 %

100 %

Rated making capacity I cm (kA, peak)

 

690 V AC

165

165

 

600 V AC

165

165

240–500 V AC

187

187

With MCR

690 V AC

165

165

600 V AC

165

165

240–500 V AC

165

165

Without instantaneous

690 V AC

94.5

94.5

500 V AC

94.5

94.5

Disconnector: switching capacity (6x I r at 690V AC)

O

O

Rated short time withstand current (kA rms)  I cw

1 s

75

75

2 s

75

75

3 s

65

65

Maximum total breaking time

ms

40 f

40 f

Closing time

ms

80

80

Number of operating cycles (ON/OFF) b

With rated current

500 V AC I n

1500

1500

690 V AC I n

1500

1500

Without rated current d

20000

20000

Connecting terminal

Horizontal terminal

O

O

Vertical terminal

O

O

Front terminal

O

O

Dimensions (HxWxD) mm

Fixed type

3-pole

410x475x290

410x475x290

4-pole

410x605x290

410x605x290

Drawout type

3-pole

430x435x368

430x435x368

4-pole

430x565x368

430x565x368

Weight kg

Fixed type

3-pole

60

61

4-pole

72

73

Drawout type (with cradle)

3-pole

92

93

4-pole

113

114

Cradle only

3-pole

35

35

4-pole

43

43

 

  1. f) This value means the instantaneous breaking time at short-circuit interruption. As for accessories (UVT, SHT)
  2. g) 4 (HN) means the neutral poles current capacity is 50 % of the rated current, for 4-poles.4 (FN) means the neutral poles current capacity is 100 % of the rated current, for 4-poles.
  3. h) () shows the value for 4P FN type.
  4. Remarks:– All models conform the isolating function according to IEC 60947-2.– Reverse connection is possible

 