Wyłączniki kompaktowe (MCCB) NF
Type/series |
WS-V series |
|||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
NF32-SV |
NF63-SV |
NF125-SV |
NF125-SGV |
NF125-SEV |
NF160-SGV |
NF250-SV |
NF250-SGV |
NF250-SEV |
||||||
S series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
32 |
63 |
125 |
125* |
125* |
160* |
250 |
250* |
250* |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
600 |
600 |
690 |
690 |
690 |
690 |
690 |
690 |
690 |
|
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
|
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
— |
— |
8/8 |
8/8 |
8/8 |
8/8 |
8/8 |
8/8 |
8/8 |
|
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
2.5/2.5 |
7.5/7.5 |
18/18 |
30/30 |
30/30 |
30/30 |
30/30 |
30/30 |
30/30 |
|
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
2.5/2.5 |
7.5/7.5 |
25/25 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
|
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
5/5 |
7.5/7.5 |
30/30 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
36/36 |
|
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
7.5/7.5 |
15/15 |
30/30 |
85/85 |
85/85 |
85/85 |
85/85 |
85/85 |
85/85 |
|
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
75x130x68 |
75/100x130x68 |
90/120/x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
|
Type |
NF125-LGV |
NF160-LGV |
NF250-LGV |
|||||||||||
L series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
125* |
160* |
250* |
||||||
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
|||||||
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
3/4 |
|||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
8/8 |
8/8 |
8/8 |
|||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
36/36 |
36/36 |
36/36 |
|||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
50/50 |
50/50 |
50/50 |
|||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
50/50 |
50/50 |
50/50 |
|||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
90/90 |
90/90 |
90/90 |
|||||||
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
|||||||
Type |
NF63-HV |
NF125-HGV |
NF125-HEV |
NF160-HGV |
NF250-HGV |
NF250-HEV |
||||||||
H series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
63 |
125* |
125* |
160* |
250* |
250* |
|||
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
690 |
690 |
690 |
||||
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
2.5/2.5 |
10/8 |
10/8 |
10/8 |
10/8 |
10/8 |
||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
7.5/7.5 |
50/38 |
50/38 |
50/38 |
50/50 |
50/50 |
||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
10/8 |
65/65 |
65/65 |
65/65 |
65/65 |
65/65 |
||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
10/8 |
75/75 |
75/75 |
75/75 |
75/75 |
75/75 |
||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
25/19 |
100/100 |
100/100 |
100/100 |
100/100 |
100/100 |
||||
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
75/100x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
||||
Type |
NF125-RGV |
NF250-RGV |
||||||||||||
R series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
125* |
250* |
|||||||
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
||||||||
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3 |
3 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
— |
— |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
— |
— |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
125/125 |
125/125 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
150/150 |
150/150 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
150/150 |
150/150 |
||||||||
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
105x165x68 |
105x165x68 |
||||||||
Type |
NF125-UV |
NF250-UV |
||||||||||||
U series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
125 |
250 |
|||||||
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
||||||||
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
10/10 |
15/15 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
200/200 |
200/200 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
200/200 |
200/200 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
200/200 |
200/200 |
||||||||
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
200/200 |
200/200 |
||||||||
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
105/140x240x68 |
105/140x240x68 |
||||||||
Type |
DSN32-SV |
DSN63-SV |
DSN125-SGV |
DSN160-SGV |
DSN250-SGV |
|||||||||
Disconnectors |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
32 |
63 |
125 |
160 |
250 |
||||
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC/DC |
600 |
600 |
690 |
690 |
690 |
|||||
Rated voltage U e [V] |
Rated voltage U e [V] |
AC (50/60 Hz)/DC |
AC (50/60 Hz)/DC |
AC (50/60 Hz)/DC |
500/250 |
500/250 |
690/300 |
690/300 |
690/300 |
|||||
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3 |
3/4 |
3/4 |
3/4 |
3/4 |
|||||
Max. switching current [A] (breaking) |
Max. switching current [A] (breaking) |
Max. switching current [A] (breaking) |
Max. switching current [A] (breaking) |
AC/DC |
256/128 |
504/252 |
1000/500 |
1280/640 |
2000/1000 |
|||||
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
75x130x68 |
75/120x130x68 |
105/140x165x68 |
105/140x165x68 |
105/140x165x68 |
a DC on request b In case of solderless terminal, interrupting capacity reduces. * adjustable
Type/series |
WS series |
||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
NF400-SEW |
NF630-SEW |
NF800-SEW |
NF1000-SEW |
NF1250-SEW |
NF1600-SEW |
||||||
S series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
400* |
630* |
800* |
1000* |
1250* |
1600* |
S series |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
690 |
690 |
690 |
S series |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
S series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
10/10 b |
10/10 |
10/10 |
25/13 |
25/13 |
25/13 |
S series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
30/30 b |
30/30 |
30/30 |
65/33 |
65/33 |
65/33 |
S series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
42/42 b |
42/42 |
42/42 |
85/43 |
85/43 |
85/43 |
S series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
50/50 b |
50/50 |
50/50 |
85/43 |
85/43 |
85/43 |
S series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
85/85 b |
85/85 |
85/85 |
125/63 |
125/63 |
125/63 |
S series |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
210/280x406x140 |
210/280x406x140 |
210/280x406x140 |
Type |
NF400-HEW |
NF630-HEW |
NF800-HEW |
||||||||
H series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
400* |
630* |
800* |
|||
H series |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
|||
H series |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
3/4 |
|||
H series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
10/10 |
15/15 |
15/15 |
|||
H series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
50/50 |
50/50 |
50/50 |
|||
H series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
65/65 |
65/65 |
65/65 |
|||
H series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
70/70 |
70/70 |
70/70 |
|||
H series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
100/100 |
100/100 |
100/100 |
|||
H series |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
|||
Type |
NF400-REW |
NF630-REW |
NF800-REW |
||||||||
R series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
400* |
630* |
800* |
|||
R series |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
690 |
|||
R series |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3 |
3 |
3 |
|||
R series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
15/10 |
20/15 |
20/15 |
|||
R series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
70/35 |
70/35 |
70/35 |
|||
R series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
125/63 |
125/63 |
125/63 |
|||
R series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
125/63 |
125/63 |
125/63 |
|||
R series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
150/75 |
150/75 |
150/75 |
|||
R series |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
140x257x103 |
140x257x103 |
210x275x103 |
|||
Type |
NF400-UEW |
NF800-UEW |
|||||||||
U series |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
400* |
800* |
||||
U series |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC |
690 |
690 |
||||
U series |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
||||
U series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
690 V |
35/35 |
35/35 |
||||
U series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
500 V |
170/170 |
170/170 |
||||
U series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
440 V |
200/200 |
200/200 |
||||
U series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
400 V |
200/200 |
200/200 |
||||
U series |
Rated breaking capacity [kA] ( I cu / I cs ) |
IEC 947-2 EN 60 947-2 VDE 0660 |
IEC 947-2 EN 60 947-2 VDE 0660 |
AC a (50/60 Hz) |
230 V |
200/200 |
200/200 |
||||
U series |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
140/280x297/322x200 |
210/280x322x200 |
||||
Type |
DSN400-SW |
DSN630-SW |
DSN800-SW |
DSN1000-SW |
DSN1250-SW |
DSN1600-SW |
|||||
Disconnectors |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
Rated current I n max. [A] |
400 |
630 |
800 |
1000 |
1250 |
1600 |
Disconnectors |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
Rated insulation voltage U i [V] |
AC/DC |
690 |
690 |
690 |
660 |
660 |
660 |
Disconnectors |
Rated voltage U e [V] |
Rated voltage U e [V] |
AC (50/60 Hz)/DC |
AC (50/60 Hz)/DC |
AC (50/60 Hz)/DC |
690/250 |
690/250 |
690/250 |
660/250 |
660/250 |
660/250 |
Disconnectors |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
Number of poles |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
3/4 |
Disconnectors |
Max. switching current [A] (breaking) |
Max. switching current [A] (breaking) |
Max. switching current [A] (breaking) |
Max. switching current [A] (breaking) |
AC/DC |
3200/1600 |
5040/2520 |
6400/3200 |
8000/14000 |
10000/5000 |
12800/6400 |
Disconnectors |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
Dimensions WxHxD |
[mm] |
140/185x257x103 |
140/185x257x103 |
210/280x275x103 |
210/280x406x140 |
210/280x406x140 |
210/280x406x140 |
* adjustable