Wyjścia
Specifications |
QY10 |
QY10-TS |
||||||
---|---|---|---|---|---|---|---|---|
Outputs |
16 |
16 |
||||||
Output type |
Relay |
Relay |
||||||
Common terminal arrangement points |
16 |
16 |
||||||
Insulation method |
Relay |
Relay |
||||||
Rated output voltage |
24 V DC/240 V AC |
24 V DC/240 V AC |
||||||
Operating voltage range |
— |
— |
||||||
Min. switching load |
5 V DC (1 mA) |
5 V DC (1 mA) |
||||||
Max. switching voltage |
125 V DC/264 V AC |
125 V DC/264 V AC |
||||||
Max. output current A |
2 |
2 |
||||||
Output current per group TYP A |
8 |
8 |
||||||
Inrush current |
— |
— |
||||||
Leakage current at OFF mA |
— |
— |
||||||
Response time |
OFF > ON ms |
≤10 |
≤10 |
|||||
ON > OFF ms |
≤12 |
≤12 |
||||||
Life |
Mechanical |
Switching 20 million times |
Switching 20 million times |
|||||
Electrical |
Switching 100000 times or more |
Switching 100000 times or more |
||||||
Max. switching frequency |
Switching 3600 times/h |
Switching 3600 times/h |
||||||
Noise suppression |
— |
— |
||||||
Fuse |
— |
— |
||||||
Power indicator |
All modules possess a status LED per output. |
All modules possess a status LED per output. |
||||||
Fuse blown indicator |
— |
— |
||||||
Connection terminal |
18-point removable terminal block with screws |
Removable terminal block with spring terminals |
||||||
Occupied I/O points |
16 |
16 |
||||||
Applicable wire size mm 2 |
0.3–0.75 |
0.3–0.75 |
||||||
Ext. power supply req. |
Voltage |
— |
— |
|||||
Current mA |
— |
— |
||||||
Internal power consumption (5 V DC) (mA) |
430 (all output points ON) |
430 (all output points ON) |
||||||
Weight kg |
0.22 |
0.22 |
||||||
Dimensions (WxHxD) mm |
27.4x98x90 |
27.4x98x90 |
||||||
Order information Art. no. |
129605 |
221841 |
||||||
Accessories |
37-pin connector, 40-pin connector and ready to use connection cables; spring clamp terminal block for exchange against the standard screw terminal block |
37-pin connector, 40-pin connector and ready to use connection cables; spring clamp terminal block for exchange against the standard screw terminal block |
Specifications |
QY41P |
QY42P |
|||||||||
---|---|---|---|---|---|---|---|---|---|---|---|
Outputs |
32 |
64 |
|||||||||
Output type |
Transistor (sink type) |
Transistor (sink type) |
|||||||||
Common terminal arrangement points |
32 |
32 |
|||||||||
Insulation method |
|||||||||||
Rated output voltage |
12/24 V DC |
12/24 V DC |
|||||||||
Operating voltage range |
10.2–28.8 V DC |
10.2–28.8 V DC |
|||||||||
Min. switching load |
— |
— |
|||||||||
Max. switching voltage |
— |
— |
|||||||||
Max. output current A |
0.1 |
0.1 |
|||||||||
Output current per group TYP A |
2 |
2 |
|||||||||
Inrush current |
0.7 A for ≤10 ms |
0.7 A for ≤10 ms |
|||||||||
Leakage current at OFF mA |
≤0.1 |
≤0.1 |
|||||||||
Response time |
OFF > ON ms |
≤1 |
≤1 |
||||||||
ON > OFF ms |
≤1 |
≤1 |
|||||||||
Life |
Mechanical |
— |
— |
||||||||
Electrical |
— |
— |
|||||||||
Max. switching frequency |
— |
— |
|||||||||
Noise suppression |
— |
— |
|||||||||
Fuse |
Short-circuit proof |
Short-circuit proof |
|||||||||
Power indicator |
|||||||||||
Fuse blown indicator |
— |
— |
|||||||||
Connection terminal |
40-pin connector |
40-pin connector x 2 |
|||||||||
Occupied I/O points |
32 |
64 |
|||||||||
Applicable wire size mm 2 |
0.3 |
0.3 |
|||||||||
Ext. power supply req. |
Voltage |
12–24 V DC |
12–24 V DC |
||||||||
Current mA |
20 (24 V DC) |
20 (24 V DC) |
|||||||||
Internal power consumption (5 V DC) (mA) |
105 (all output points ON) |
150 (all output points ON) |
|||||||||
Weight kg |
0.15 |
0.17 |
|||||||||
Dimensions (WxHxD) mm |
27.4x98x90 |
27.4x98x90 |
|||||||||
Order information Art. no. |
132576 |
132577 |