Regulacja z pętlą sprzężenia zwrotnego
Specifications |
Q62HLC |
||
---|---|---|---|
Number of input channels |
2 |
||
Analog input |
Thermocouple |
°C |
-200–2300 (0.1 °C resolution) |
Micro voltage |
mV |
-100–100 (0.5–10 µV resolution) |
|
Voltage |
V |
-10–10 (0.05–1 mV resolution) |
|
Current |
mA |
0–20 (0.8–1 µA resolution) |
|
Digital output |
-2000–23000, -10000–10000, -10000–10000, 0–20000 |
||
Supported thermocouples |
K, J, T, S, R, N, E, B, PL II, W5re/W26Re |
||
Max. conversion speed |
25 ms/2 channels |
||
Normal mode rejection ratio |
60 dB or more (50/60 Hz) |
||
Common mode rejection ratio |
120 dB or more (50/60 Hz) |
||
Input filter (primary delay digital filter) |
0.0–100.0 s |
||
Sensor compensation value setting |
-50.00–50.00 % |
||
Control method |
Continuous proportional control |
||
PID constant range |
PID constant setting |
Setting possible by auto-tuning |
|
Proportional band (P) |
Thermocouple: 0.1 to full scale °C; micro voltage, voltage, current: 0.1–1000.0 % |
||
Integral time (I) |
s |
0.0–3276.7 |
|
Differential time (D) |
s |
0.0–3276.7 |
|
Set value setting range |
Thermocouple: input range of thermocouple being used |
||
Dead band setting range |
0.1–10.0 % |
||
Occupied I/O points |
16 |
||
Isolation |
Transformer isolation between the input channels and between the inputs and ground |
||
Connection terminals |
18-point removable terminal block with screws |
||
Applicable wire size |
mm 2 |
0.3–0.75 |
|
External power supply |
24 V DC, 70 m A |
||
Internal power consumption (5 V DC) |
mA |
270 |
|
Weight |
kg |
0.25 |
|
Dimensions (WxHxD) |
mm |
27.4x98x112 |
|
Order information Art. no. |
200693 |