Rozszerzenie wejść/wyjść
Powered extension units
Specifications |
FX2N-32ER-ES/UL |
FX2N-32ET-ESS/UL |
|||||
---|---|---|---|---|---|---|---|
Electrical data |
|||||||
Integrated inputs/outputs |
32 |
32 |
|||||
Power supply |
AC range (+10 %, -15 %) |
100–240 V |
100–240 V |
||||
Frequency at ACHz |
50/60 |
50/60 |
|||||
DC range (+20 %, -30 %) |
— |
— |
|||||
Max. input apparent power |
35 VA |
35 VA |
|||||
Inrush current at ON |
100 V AC |
40 A<5 ms |
40 A<5 ms |
||||
200 V AC |
60 A<5 ms |
— |
|||||
Allowable momentary power failure time ms |
10 |
10 |
|||||
External service power supply (24 V DC) mA |
250 |
250 |
|||||
Power supply int. bus (5 V DC) mA |
690 |
690 |
|||||
Inputs |
|||||||
Integrated inputs |
16 |
16 |
|||||
Min. current for logical 1 mA |
3.5 |
3.5 |
|||||
Max. current for logical 0 mA |
1.5 |
1.5 |
|||||
Response time |
For all extension units of the MELSEC FX2N series: 10 ms (at time of shipment) |
For all extension units of the MELSEC FX2N series: 10 ms (at time of shipment) |
|||||
Outputs |
|||||||
Integrated outputs |
16 |
16 |
|||||
Output type |
Relay |
Transistor (source) |
|||||
Switching voltage (max.) |
Generally for relay version: <264 V AC, <30 V DC; for transistor version: 5–30 V DC |
Generally for relay version: <264 V AC, <30 V DC; for transistor version: 5–30 V DC |
|||||
Max. output current |
- per output A |
2 |
0.5 |
||||
- per group* A |
8 |
0.8/1.6 b |
|||||
Max. switching power |
- inductive load W |
80 |
12 |
||||
Response time ms |
10 |
<0.2 |
|||||
Life of contacts (switching times) a |
For all extension units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (for relay output only) |
For all extension units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (for relay output only) |
|||||
Mechanical data |
|||||||
Weight kg |
0.65 |
0.65 |
|||||
Dimensions (WxHxD) mm |
150x90x87 |
150x90x87 |
|||||
Order information Art. no. |
65568 |
65569 |
- Not guaranteed by Mitsubishi Electric
- 0.8 for 4 per group and 1.6 for 8 per group* This limitation applies only per reference terminal for each group. Please observe the terminal assignments for the group identification.
Unpowered extension units
Specifications |
FX2N-8ER-ES/UL |
FX2N-8EX-ES/UL |
||||||
---|---|---|---|---|---|---|---|---|
Electrical data |
||||||||
Integrated inputs/outputs |
8 |
8 |
||||||
Number of occupied I/O points in the PLC |
16 |
8 |
||||||
Power supply |
All modular extension blocks are supplied by the base unit. |
All modular extension blocks are supplied by the base unit. |
||||||
Inputs |
||||||||
Integrated inputs |
4 |
8 |
||||||
Min. current for logical 1 mA |
3.5 |
3.5 |
||||||
Max. current for logical 0 mA |
1.5 |
1.5 |
||||||
Response time |
For all extension blocks of the MELSEC FX2N series: 10 ms (at time of shipment) |
For all extension blocks of the MELSEC FX2N series: 10 ms (at time of shipment) |
||||||
Outputs |
||||||||
Integrated outputs |
4 |
— |
||||||
Output type |
Relay |
— |
||||||
Switching voltage (max.) |
Generally for relay version: <240 V AC, <30 V DC; for transistor version: 5–30 V DC |
Generally for relay version: <240 V AC, <30 V DC; for transistor version: 5–30 V DC |
||||||
Max. output current |
- per output A |
2 |
— |
|||||
- per group a A |
8 |
— |
||||||
Max. switching power |
- inductive load VA |
80 |
— |
|||||
Response time ms |
10 |
10 |
||||||
Life of contacts (switching times) b |
For all extension units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (for relay output only) |
For all extension units of the MELSEC FX2N series: 3,000,000 at 20 VA; 1,000,000 at 35 VA; 200,000 at 80 VA (for relay output only) |
||||||
Mechanical data |
||||||||
Weight kg |
0.2 |
0.2 |
||||||
Dimensions (WxHxD) mm |
43x90x87 |
43x90x87 |
||||||
Order information Art. no. |
166285 |
166284 |
- This limitation applies only per reference terminal for each group. Please observe the terminal assignments for the group identification.
- Not guaranteed by Mitsubishi ElectricNote: To connect these modules to a FX3GC base unit, an adapter FX2N-CNV-IF or a power supply FX3UC-1PS-5V is required.
Unpowered extension modules
Specifications |
FX2NC-16EX-T-DS |
FX2NC-16EYR-T-DS |
|||||
---|---|---|---|---|---|---|---|
Electrical data |
|||||||
Integrated inputs/outputs |
16 |
||||||
Power supply |
All modular extension blocks are supplied by the base unit. |
All modular extension blocks are supplied by the base unit. |
|||||
Inputs |
|||||||
Integrated inputs |
16 |
— |
|||||
Input current X0 → X7 / X10 →∞ |
7/5 |
— |
|||||
Min. current for logical 1 X0 → X7/X10 →∞ mA |
4.5/3.5 |
— |
|||||
Max. current for logical 0mA |
1.5 |
— |
|||||
Isolation |
Photocoupler isolation between input terminals and PC power for all base units |
Photocoupler isolation between input terminals and PC power for all base units |
|||||
Response time |
For all extension units of the MELSEC FX2NC series: 10 ms (at time of shipment), partly adjustable between 0 and 60 ms in 1 ms steps (REFF, FNC51 = 0–60 ms) |
For all extension units of the MELSEC FX2NC series: 10 ms (at time of shipment), partly adjustable between 0 and 60 ms in 1 ms steps (REFF, FNC51 = 0–60 ms) |
|||||
Outputs |
|||||||
Integrated outputs |
— |
16 |
|||||
Output type |
— |
Relay |
|||||
Switching voltage (max.) V |
Generally for relay version: <240 V AC, <30 V DC; for transistor version: 5–30 V DC |
Generally for relay version: <240 V AC, <30 V DC; for transistor version: 5–30 V DC |
|||||
Max. output current |
- per output A |
— |
2 |
||||
- per group* A |
— |
4/8 |
|||||
Max. switching power |
- inductive load VA |
— |
80 |
||||
- lamp load W |
— |
100 |
|||||
Response time ms |
— |
10 |
|||||
Life of contacts (switching times) |
— |
like base unit |
|||||
Mechanical data |
|||||||
Connection type |
Removable screw terminal blocks |
Removable screw terminal blocks |
|||||
Weight kg |
0.2 |
0.2 |
|||||
Dimensions (WxHxD) mm |
20.2x90x89 |
20.2x90x89 |
|||||
Order information Art. no. |
128152 |
128153 |
a 0.3 A for Y0 to Y1; 0.1 A all others b 7.2 W for Y0 to Y3; 2.4 W all others c 0.9 W for Y0 to Y3; 0.3 W all others
* This limitation applies only per reference terminal for each group. Please observe the terminal assignments for the group identification.
Note: These modules can be combined with PLC base units of the FX3GC or FX3UC series!